Expand description
Voltage dependent load power: the one evaluation of a balanced load’s
LoadVoltageModel at a bus voltage magnitude, with its derivative.
With x = vm / vn, the bus voltage magnitude against the load’s nominal
voltage (both per unit on the bus base), a load draws
P(vm) = p - Σ c_k + Σ c_k x^γ_k (and Q alike)where p is the stated Load::p and each term c_k x^γ_k is a ZIP
constant current part (γ = 1), a ZIP constant impedance part (γ = 2),
or an exponential side (its γ, when not zero). The stated power stays
authoritative for everything beyond the terms: the ZIP constant power
part, an exponential γ = 0 side, or a demand edit written onto p.
Structs§
- Load
Power AtVoltage - A load’s power at a voltage magnitude, in its own unit, with the derivatives with respect to the magnitude.
- Load
Voltage Term - One voltage dependent part of a load:
coefficient · (vm / v_nom)^exponentin the load’s power unit.
Enums§
- Load
Voltage Error - Why a load’s voltage model cannot be evaluated.
Constants§
- LOAD_
VOLTAGE_ RATIO_ FLOOR - The voltage ratio floor of the one power law term evaluation
(
powerio_core::electrical::calc_voltage_power_term). Below this voltage ratio a power law term with exponent below one is continued by its tangent at the floor (calc_voltage_power_term):x^γhas an unbounded slope at zero forγ < 1(and is itself unbounded forγ < 0), and an iterate can pass near zero on its way to a solution.
Functions§
- calc_
load_ nominal_ voltage - A load’s nominal voltage in per unit on its bus base.