HVDC lines as fixed bus injections.
A balanced calculation has no DC network: an Hvdc line couples its two
AC terminal buses only through the power its converters exchange with
them. The calculations therefore carry each in service line as two fixed
injections at its stated operating point.
The calculation interface is the bus-to-device terminal view,
Hvdc::calc_bus_to_device_powers: at each end, active and reactive
power are positive from that end’s AC bus into the HVDC system (the two
converters and the DC line taken as one device), the direction AC branch
terminal flows use. The two active terminal powers sum to the power the
line and its converters lose, and the injection into each bus is the
negative of that end’s terminal power, negated once in
Hvdc::calc_terminal_injections.
The stored fields pf, pt, qf, and
qt keep MATPOWER’s dcline signs throughout 0.11.x, whatever
the source format: pf is positive from the from bus into the line, while
pt, qf, and qt are positive from the line into their bus. The
terminal view converts them once: p_from = pf, q_from = -qf,
p_to = -pt, q_to = -qt. The injections match MATPOWER’s
toggle_dcline dummy generators.
Structs§
- Hvdc
Injections - Every fixed HVDC injection a network states, with the lines that make
none. Build it with
BalancedNetwork::calc_hvdc_injections. - Hvdc
Terminal Injection - The injection one HVDC line makes at one of its AC terminal buses.
- Hvdc
Terminal Powers - The bus-to-device terminal powers of one HVDC line: at each end, active
and reactive power positive from that end’s AC bus into the HVDC system
(both converters and the DC line taken as one device). Build it with
Hvdc::calc_bus_to_device_powers.
Enums§
- Hvdc
Treatment - How a calculation treats the network’s HVDC lines.