pub fn calc_transformer_winding_admittance(
transformer: &DistTransformer,
) -> Result<Option<Vec<Vec<Complex<f64>>>>, Error>Expand description
The winding domain admittance Y_1Volt of a multiwinding transformer,
siemens at a one volt winding base (OpenDSS CalcY_Terminal): the
pairwise nameplate leakage impedances of
calc_transformer_leakage_impedances scaled by phases / S_1, reduced
against the last winding (calc_reduced_leakage), inverted, and lifted
back through the winding difference incidence A (row i is
u_i - u_n): Y_1Volt = Aᵀ ZB⁻¹ A. A two winding unit reduces to
y · [[1, -1], [-1, 1]]. None when the reduced matrix is exactly
singular or not finite: one volt base impedances of high rating units sit
far below any fixed pivot threshold, so only exact singularity is
refused.
§Errors
The leakage data calc_transformer_leakage_impedances refuses, or a
phase count of zero.