pub fn calc_transformer_magnetizing(
transformer: &DistTransformer,
) -> Result<Option<TransformerMagnetizing>, Error>Expand description
The magnetizing branch a transformer states, in one of three spellings:
no_load_shunt{winding, g, b}: per coil siemens on the stated one based winding;g_no_loadandb_no_load(BMOPF): siemens on the second winding, or the first winding of a regulator, divided across the phases of asingle_phase,wye_deltaordelta_wyeunit, which state a total;- OpenDSS
%noloadlossand%imag: percent of the first winding’s rating over the second winding’s coil voltage (calc_coil_voltagetimes tap), on the second winding, the susceptance inductive.
None when none is stated. The one magnetizing branch: the transformer
primitive stamps it and the multiconductor OPF descriptor writes it as
coil shunts.
§Errors
no_load_shunt beside g_no_load or b_no_load, a no_load_shunt
that is not an object of a winding, g and b alone, a winding outside
the unit, a negative or nonfinite conductance, a nonfinite susceptance,
or OpenDSS percentages that are negative or nonfinite.