Skip to main content

calc_phase_components

Function calc_phase_components 

Source
pub fn calc_phase_components(
    sequence: [Complex64; 3],
    rotation: SequenceRotation,
) -> [Complex64; 3]
Expand description

The three phase phasors [a, b, c] of zero, positive and negative sequence components [V₀, V₁, V₂]: Va = V₀ + V₁ + V₂, Vb = V₀ + a² V₁ + a V₂, Vc = V₀ + a V₁ + a² V₂ under rotation, the inverse of calc_sequence_components. The GridLAB-D sequence voltage substation reads it.