pub fn calc_potential_coefficient(image_distance: f64, distance: f64) -> f64Expand description
Maxwell’s potential coefficient between two conductors (without the
1 / 2πε factor): ln(S / D), with S the distance to the other
conductor’s earth image and D the direct distance. A conductor’s self
coefficient takes S = 2h and D its radius. The one potential
coefficient: the OpenDSS and GridLAB-D geometry capacitances read it.