pub fn calc_connection_channels(
configuration: Configuration,
terminal_count: usize,
channel_count: usize,
neutral: Option<usize>,
) -> Result<Vec<ConnectionChannel>, String>Expand description
The channels of a connection of terminal_count terminals carrying
channel_count stated powers, one channel per power in power order:
- single phase or delta, two terminals and one power: the first terminal to the second;
- wye or single phase, one terminal per power: each terminal to ground;
- wye with one terminal more than its powers: each phase terminal to the
neutral, the terminal at
neutralor else the last; - delta with two terminals per power: each consecutive pair, the first of the pair to the second;
- delta with one terminal per power: a ring, terminal
kto terminalk + 1, the last back to the first.
neutral is read only for a wye with an explicit neutral. The one
connection rule: the LinDist3Flow incidence, the GridLAB-D writer,
calc_element_connection (every load, capacitor, inverter, source and
transformer winding the multiconductor calculations connect) read it.
ยงErrors
A configuration and arity that describe none of these connections, or a
neutral position outside the terminal map.