pub fn calc_capacitor_susceptance(
network: &MulticonductorNetwork,
capacitor: &DistCapacitor,
) -> Result<Option<ConductorMatrix>, String>Expand description
A capacitor bank’s susceptance matrix, siemens, over its terminal map.
Each coil of the bank’s connection (calc_element_connection: a WYE
coil from each phase to its neutral or to ground, a DELTA coil between
consecutive terminals or across a two terminal bank, a single phase coil
across its two terminals) carries an equal share of the rated reactive
power at its coil voltage:
b = q_rated / coils / V², V = v_nom / √3 (WYE with more than one terminal), v_nom otherwiseThe WYE nameplate is line to line when the bank has an explicit return
or several phases; a one terminal WYE bank states its coil voltage.
None for a configuration with no capacitor connection. The one
capacitor stamp: the multiconductor admittance matrix
(powerio_matrix::calc_capacitor_primitive_admittance), the PMD and PMD
MATHEMATICAL writers and the LinDist3Flow preparation read it.
§Errors
A nameplate that is not finite with a positive voltage, or a terminal map its configuration cannot carry (an undeclared bus, an ambiguous WYE neutral, a single phase bank without two terminals).